    Width Height Weight Catalog Watts Volts Amps In. (mm) In. (mm) lb (kg) Number 24 x 24

    250 120 24 (610) 24 (610) 2.1 15 (6.8) AS2424-250-120? 250 240 24 (610) 24 (610) 1.0 15 (6.8) AS2424-250-240? 250 277 24 (610) 24 (610) 0.9 15 (6.8) AS2424-250-277? 310 120 24 (610) 24 (610) 2.6 15 (6.8) AS2424-310-120? 310 208 24 (610) 24 (610) 1.5 15 (6.8) AS2424-310-208? 310 240 24 (610) 24 (610) 1.3 15 (6.8) AS2424-310-240? 310 277 24 (610) 24 (610) 1.1 15 (6.8) AS2424-310-277? 325 240 24 (610) 24 (610) 1.4 15 (6.8) AS2424-325-240? 335 120 24 (610) 24 (610) 2.8 15 (6.8) AS2424-335-120? 335 277 24 (610) 24 (610) 1.2 15 (6.8) AS2424-335-277? 355 208 24 (610) 24 (610) 1.7 15 (6.8) AS2424-355-208? 375 120 24 (610) 24 (610) 3.1 15 (6.8) AS2424-375-120? 375 208 24 (610) 24 (610) 1.8 15 (6.8) AS2424-375-208? 375 277 24 (610) 24 (610) 1.4 15 (6.8) AS2424-375-277? 24 x 48

    500 120 24 (610) 48 (1219) 4.2 30 (13.6) AS2448-500-120? 500 240 24 (610) 48 (1219) 2.1 30 (13.6) AS2448-500-240? 500 277 24 (610) 48 (1219) 1.8 30 (13.6) AS2448-500-277? 535 208 24 (610) 48 (1219) 2.6 30 (13.6) AS2448-535-208? 625 120 24 (610) 48 (1219) 5.2 30 (13.6) AS2448-625-120? 625 208 24 (610) 48 (1219) 3.0 30 (13.6) AS2448-625-208? 625 240 24 (610) 48 (1219) 2.6 30 (13.6) AS2448-625-240? 660 277 24 (610) 48 (1219) 2.4 30 (13.6) AS2448-660-277? 715 208 24 (610) 48 (1219) 3.4 30 (13.6) AS2448-715-208? 725 240 24 (610) 48 (1219) 3.0 30 (13.6) AS2448-725-240? 750 120 24 (610) 48 (1219) 6.3 30 (13.6) AS2448-750-120? 14 x 48

    300 240 14 (356) 48 (1219) 1.3 18 (8.2) AS1448-300-240? 350 120 14 (356) 48 (1219) 2.9 18 (8.2) AS1448-350-120? 350 277 14 (356) 48 (1219) 1.3 18 (8.2) AS1448-350-277? 400 208 14 (356) 48 (1219) 1.9 18 (8.2) AS1448-400-208? 435 208 14 (356) 48 (1219) 2.1 18 (8.2) AS1448-435-208? 435 240 14 (356) 48 (1219) 1.8 18 (8.2) AS1448-435-240? 435 277 14 (356) 48 (1219) 1.6 18 (8.2) AS1448-435-277? 14 x 60

    350 120 14 (356) 60 (1524) 2.9 22 (10.0) AS1460-350-120? 375 240 14 (356) 60 (1524) 1.6 22 (10.0) AS1460-375-240? 375 277 14 (356) 60 (1524) 1.4 22 (10.0) AS1460-375-277? 450 208 14 (356) 60 (1524) 2.2 22 (10.0) AS1460-450-208? 535 277 14 (356) 60 (1524) 1.9 22 (10.0) AS1460-535-277? 550 240 14 (356) 60 (1524) 2.3 22 (10.0) AS1460-550-240? ?Add finish code.

    90-3110-83

    RADIANT CEILING PANELS

    AS SERIES SUBMITTAL

    Page 2 of 6

Factory Built-in Options Finishes?

    Code Description Code Description Specify custom color finish. O Standard finish; textured white baked-on Flexible electrical conduit. Specify length of PT FCXX powder coating on front panel. conduit XX-inches. List per Foot. 304 Stainless steel construction, includes 36” Silicone seams, provides protection in high S304 of sealtite conduit and silicone seal. Smoisture areas. Includes 36” of sealtite 316 Stainless steel construction, includes 36” conduit. S316 of sealtite conduit and silicone seal. Tegular reveal edge detail for 15/16” grid. TEG Silk screen to match acoustical ceiling tiles TEGFFineline Tegular reveal edge for 9/16” grid. (specify style). SS One time set-up fee if pattern is not in stock. Field-Installed Options

    (shipped loose for field installation into heaters) Control Options

    Catalog Width Length Weight Catalog Number In. (mm)In. (mm)lb (kg)Description Number

    Surface Mounting Frames SmartRooms low voltage controller.

    Sensor(s) must be ordered at the same SF-22? 24 (610)24 (610)4 (1.8) SR-LV time. SF-24? 24 (610)48 (1219)9 (4.1) Requires connection to SmartRooms SF-1448? 14 (356)48 (1219)8 (3.6) Communication Panel.

    SF-1460? 14 (356)60 (1524)10 (4.5) Plaster ring for SR-LV Controller PL-1 Plaster Mounting Frames Box ring for SR-240/120 Controller BX-1 PF-22? 24 (610)24 (610)2 (1.0)Used with SR-240/120, 15’ long Sensors PF-24? 24 (610)48 (1219)4 (1.8) Longer length add per foot SPF-24(1) 24 (610)48 (1219)4 (1.8) SmartRooms Panel w/10comm. Ports SRDP-10/10 PF-1448? 14 (356)48 (1219)5 (2.3)and 10 ea. 20 amp relays SmartRooms Panel w/10comm. Ports PF-1460? 14 (356)60 (1524)6 (2.7) SRDP-10/20 and 20 ea. 20 amp relays Filler Panel SmartRooms Panel w/20comm. Ports SRDP-20/20 Sized and finished to match standard, and 20 ea. 20 amp relaysFP custom color or silk screened panel ? Add finish code.

    (1) Stainless steel frame, specify 304 or 316 type.

    Thermostats for AS Series Radiant Ceiling Panels

    Positive Temperature Switch Tamper- Amps @ Pilot Catalog Number Color Type Thermometer Amps @ 277V o Typeproof120-240VDutyOffRange F

    16A @ (4) SR-240/120Electronic White DPDT No Digital -- -- -- 41-95 120 & 240V

    R-101 SPST No No -- No 40-85 Bimetal Beige 22 18 R-102 DPST No No -- Yes 40-85 (4) A 3 inch deep double electrical box will be supplied for wall installation. Remote window sensor option is available, contact factory for pricing.

    90-3110-83

RADIANT CEILING PANELS

    AS SERIES SUBMITTAL

    Page 3 of 6

Notes:

    (1) All panels are single-phase.

    (2) Standard finish is a textured white baked on powder coat. (3) Standard panels are furnished with a 4” x 4” x 1-? junction box with cover for field electrical connection. (4) Corner support clips are furnished on each panel. Clips have holes for support wires/chains for mounting and

     earthquake requirements.

     WIRING DIAGRAM FOR ARCHITECTURAL SERIES HEATERS

    208V120, 220,120/240120/240or230, 277@240@120240Vor 347V3 WIRE3 WIRE2 WIRE2 WIREHEATERHEATERHEATERHEATER

    120V208V120V240V240V220V230V277V347V

RADIANT CEILING PANELS

    AS SERIES SUBMITTAL

    Page 4 of 6 2 INCHES, 4.0 LB DENSITYHIGH TEMPERATURE MINERAL WOOL INSULATIONSUPPORT CLIPS

    22 GAUGE GALVANIZED REFLECTIVEHIGH DENSITYSTEEL FRONT AND BACKFOILHEATING PANEL OF UNIT

    4" X 4" X 1-1/2" JUNCTION BOXFACTORY FINISHED WITHELECTRIC HEATINGWITH COVERA HIGH TEMPERATURE,ELEMENT - ALLOY WIRE, TEXTURED ACRYLICTEFZEL INSULATIONLATEX PAINT

    2"

    Cutaway View of

    Architectural Series HeaterBA

    CEILING JOIST

    RADIANT HEATER

    EACH KIT INCLUDES:JUNCTION BOX2 - SIDE PIECES4" x 4" 1-1/2"2 - END PIECES4 - CORNER BRACKETSNAIL

    2"

    2"FLUSH MOUNTING FRAME1-1/2"FACTORY PAINTED 24 GAUGEEXTRUDED ALUMINUM

    Plaster FrameFINISHED CEILING

    Flush Mount Kit

RADIANT CEILING PANELS

    AS SERIES SUBMITTAL

    Page 5 of 6

    POWER SUPPLY

     CEILING JOIST

     EACH KIT INCLUDES:

     2 - SIDE CHANNELSTOGGLE BOLT2 - END CHANNELS 4 - CORNER BRACKETS

     WITH SCREWS

     CORNER MOUNTING4"CEILING BRACKET WITH SCREWS2"

     SURFACE MOUNTING FRAME4" X 4" X 1-1/2"JUNCTION BOXFACTORY PAINTED 12 GAGE

    GALVANIZED STEELRADIANT HEATER

    Surface Mounting

    Flush Mount Frame

    in Drywall CeilingWire SuspendedFlush Mounting Kit

    NAIL

    CEILING JOIST

    RADIANT CEILING PANELS

    AS SERIES SUBMITTAL

    Page 6 of 6

    Architect’s and Engineer’s Specifications

    1. Electric radiant ceiling panels shall be by INDEECO, construction and options as shown below. Panels

    shall be CSA Certified, for the wattage, voltage and size as specified in the schedule. US

    2. Panels shall use a high quality alloy resistance wire element electrically insulated with an approved

    TEFZEL compound rated at 200;C. The heating element is uniformly arranged over the entire face of

    the panel to provide evenly distributed radiant heat. High-efficient reflective foils are used to adhere the

    heating element to the radiant panel.

    23. Panels are to be designed with a watt density range of 65-95 watts/ft at rated voltage.

    4. The panel shall contain two-inch thick, four-pound density high temperature mineral wool insulation.

    Fiberglass insulation is not acceptable.

    5. Panel shall be constructed from heavy 22 gauge galvanized steel. Front panel shall be finished with a

    white textured high temperature baked on powder coat. Textured finish enhances the radiant effect by

    providing a wider scattering of the radiant energy, increasing the panels overall efficiency. 6. Panels will be a two-piece construction crimped together for strength and rigidity. Pop rivet

    construction is not acceptable.

    7. Panel shall be provided with an electrical junction box attached to the back of the panel. Junction box

    shall be 4 x 4 x 1-1/2 inches and shall be provided with a cover. Internal pigtail wires shall be provided

    for field wiring connection.

    8. Hanging/support clips in each corner shall be provided for local code and earthquake installation

    requirements.

    9. Provide special finishes. [Check off one of the following options]:

     Radiant panels to be silk-screened to match sample provided of architectural ceiling title.

     Custom color panels to match color sample provided. Finish to be baked on high temperature

    powder coat.

     Stainless steel panel with 36-inch long sealtite conduit and silicone seal seam.

     304 grade stainless steel.

     316 grade stainless steel.

    10. Provide panel with the following optional mounting system. [Check off one of the following options]:

     Surface mounting frame kits sized to radiant panel heater.

     Plaster mounting frame kits sized to radiant panel heater.

     Radiant panel with Tegular reveal edge for 15/16-inch grid.

     Radiant panel with Fineline Tegular reveal edge for 9/16-inch grid.

    11. Additional special features. [Check off options to be included]:

     Sealtite flexible conduit and connectors for use in high moisture areas. See schedule for conduit

    length.

     Silicone sealed seams for moisture protection in high moisture areas.

    12. The following accessories shall be factory furnished for field installation. [Check off options to be

    included]:

     Filler panels to match panel style and finish. Provides a continuous appearance along ceiling line.

     Wall mounted thermostat.