DOC

15410 - Plumbing Fixtures and Trim

By Nicholas Mcdonald,2014-11-22 07:06
10 views 0
15410 - Plumbing Fixtures and Trim

Section Cover Page

     Section 15410 2004-12-30 Plumbing Fixtures and Trim

    This Master Specification Section contains:

.1 This Cover Sheet

.2 Data Sheet Reference Standards

.3 Specification Section Text:

    1. General

    1.1 Reference Documents

    1.2 Regulatory Requirements

    1.3 Certifications

    1.4 Source of Supply

    1.5 Coordination

    2. Products

    2.1 Fixture Brass and Accessories

    2.2 Water Closet Siphon Action, with Flush Valve

    2.3 Water Closet Siphon Action, with Flush Tank

    2.4 Water Closet Reverse Trap, Floor Mount

    2.5 Urinal

    2.6 Lavatories

    2.7 Stainless Steel Sinks

    2.8 Bathtub (and Shower)

    2.9 Cabinet Shower

    2.10 Institutional Showers

    2.11 Drinking Fountain

    2.12 Wash Fountains

    2.13 Service or Mop Sinks

    2.14 Thermostatic Mixing Valve

    3. Execution

    3.1 Installation

    3.2 Protection

    3.3 Fixtures Rough-In Schedule

END OF DATA SHEETS

    BMS Basic Master Specification Alberta Infrastructure and Transportation Page 01 Master Specification System

     Section 15410

    Plan No: Plumbing Fixtures and Trim

    Project ID: Page 1

1. General

1.1 REFERENCE DOCUMENTS

    .1 Plumbing fixtures shall meet or exceed CAN/CSA-B45 Series-02, Plumbing Fixtures

    [and CAN/CSA-Z317.1-99 (R2002), Special Requirements for Plumbing Installations in

    Health Care Facilities].

SPEC NOTE: Specify CAN/CSA-Z317.1 only for Health Care Facilities.

1.2 PRODUCT OPTIONS AND SUBSTITUTIONS

    SPEC NOTE: Refer to Section 00760 for projects less than $100,000.00 only

    .1 Refer to Section [00760] [01621] for requirements pertaining to product options and

    substitutions.

1.3 REGULATORY REQUIREMENTS

    .1 Plumbing fixtures shall be approved by the authority having jurisdiction.

1.4 CERTIFICATIONS

    .1 Plumbing fixtures shall be tested, certified and labelled in accordance with a certification

    program accredited by the Standards Council of Canada. Where a product is not so

    labelled, provide written approval by the authority having jurisdiction.

1.5 SOURCE OF SUPPLY

    .1 Each of the following products shall be by a single manufacturer:

    .1 [Fixtures of the same type or group].

    .2 [Fittings of the same type].

    .3 [ ].

1.6 COORDINATION

    .1 Check millwork shop drawings. Confirm location and size of fixtures and openings

    before rough-in and installation.

2. Products

2.1 FIXTURE BRASS AND ACCESSORIES

    .1 Visible parts of fixture brass and accessories shall be heavily chrome plated.

     Section 15410

    Plan No: Plumbing Fixtures and Trim

    Project ID: Page 2

2.2 WATER CLOSET SIPHON ACTION, WITH FLUSH VALVE

    .1 Bowl: [Floor mounted] [Wall-hung] siphon action, vitreous china closet bowl with

    elongated rim, 6.0 lpf, 40 mm spud, [Crane 3325 - Whirlton] [Crane 3446 - Placidus].

    .2 Flush Valve: Exposed chrome plated, diaphragm type with oscillating handle,

    escutcheon, bumper, integral screwdriver stop and vacuum breaker,

    [Delany Flushboy # F402-1.6].

    .3 Seat: Extra heavy duty, solid [black] [white] plastic, open front, extended back, less cover,

    complete with self-sustaining hinge, [Olsonite # 95 SS].

2.3 WATER CLOSET SIPHON ACTION, WITH FLUSH TANK

    .1 Bowl: Floor mounted, 6.0 lpf, siphon action, vitreous china, 438 mm high close-coupled

    closet combination with elongated rim insulated tank, flapper type flush valve, and china

    bolt caps, [Crane 31056 Hymont Plus].

    .2 Seat: Extra heavy duty, solid [black] [white] plastic, open front, extended back, less

    cover, complete with self-sustaining hinge, [Olsonite # 95 SS].

2.4 WATER CLOSET - REVERSE TRAP, FLOOR MOUNT

    .1 Bowl: Floor mounted, 6.0 lpf, vitreous china, reverse trap, close-coupled closet

    combination with regular rim, insulated tank, flapper type flush valve, and china bolt caps,

    [Crane 3433 Cora ULF].

    .2 Seat: Solid plastic with closed front and cover, brass bolts, [Olsonite # 40].

2.5 URINAL

    .1 Urinal: Vitreous china, wall-hung, wash-out urinal with shields, integral trap, integral

    flush rim, removable SS strainer, 20 mm top spud, [Crane 7397 Cromwell].

    .2 Flush Valve: Exposed chrome plated, diaphragm type with [oscillating handle], [push

    plate] escutcheon, integral screwdriver stop, [vacuum breaker], [Delany Flushboy

    # F451-1].

    .3 Metering Valve: Exposed chrome plated, porous felt type for 15 mm supply with

    [oscillating handle] [push button] screwdriver stop, [vacuum breaker]

    [Waltec 86T Tempus].

    .4 Tank: Vitreous china insulated tank with bottom supply and siphon valve,

    [Crane Belmont].

     Section 15410

    Plan No: Plumbing Fixtures and Trim

    Project ID: Page 3

2.6 LAVATORIES

    .1 Lavatory: Wall-hung 500 x 450 mm minimum, vitreous china lavatory with minimum

    100 mm high back, drillings on [200 mm] [100 mm] centres, rectangular basin with

    splash lip and overflow, [Crane Harwich].

    .2 Lavatory: Wall-hung 480 x 430 mm minimum, vitreous china lavatory with shelf back,

    drillings on [200 mm] [100 mm] centers, rectangular basin with splash lip and overflow,

    [Crane Westmount].

    .3 Lavatory: Self-rimming countertop 530 x 450 mm minimum porcelain on steel lavatory

    with drillings on [200 mm] [100 mm] centres, overflow, seal of putty, caulking or

    concealed vinyl gasket, [Crane Marquis].

    .4 Trim: Deck mounted, [100 mm] [200 mm], chrome plated supply fitting, ? turn

    cartridge, grid drain, aerator, single wing handles, [Chicago Faucet # 802-1000CP]

    [Chicago Faucet 404-1000CP].

    .5 Trim: Chrome plated metered mixing faucet with [aerator] [spray] and coverplate,

    [Chicago Faucet # 844-E12-665 PSHCP] [Chicago Faucet # 844-665PSHCP].

2.7 STAINLESS STEEL SINKS

    .1 Bowl: 520 x 510 x 180 mm O.D., Type 302SS, self-rimming, single compartment with

    undercoating, 90 mm crumb cups, [2] [3] [4] hole drilling in ledgeback, [Kindred

    LBS 6807].

    .2 Bowl: 790 x 520 x 180 mm O.D., Type 302SS, self-rimming, double compartment with

    undercoating, 90 mm crumb cups, [2] [3] [4] hole drilling in ledgeback, [Kindred

    LBD 6407].

    .3 Trim: Chrome plated supply with swing spout, aerator, single wing handles [and

    retractable spray], [Chicago Faucet # 1100-XKCP] [Chicago Faucet # 1102-CP].

2.8 BATHTUB (AND SHOWER)

    .1 Bathtub: 1524 mm steel tub, stain resisting, porcelain on steel bathtub [with slip resistant

    surface], [Crane 2-142 Neu-Chateau].

    .2 Trim: Concealed shower and overrim supply with diverter spout, lever handles, bent

    shower arm with adjustable spray ball joint shower head and escutcheon, [Chicago

    Faucet # 749-8-370CPR], lever operated pop-up waste and overflow, curtain rod with

    snap hooks.

     Section 15410

    Plan No: Plumbing Fixtures and Trim

    Project ID: Page 4

    .3 Trim: Concealed shower and overrim supply with diverter spout, thermostatic and

    pressure balancing mixing valve, bent shower arm with adjustable spray ball joint shower

    head and escutcheon, [Chicago Faucet # 2500-600CP], lever operated pop-up waste and

    overflow, curtain rod with snap hooks.

    2.9 CABINET SHOWER

    .1 Cabinet: 800 x 800 x 1900 mm high cabinet made of 24 gauge galvanized bonderized

    steel with white baked enamel finish, ‘SMC plastic receptor, soap dish, curtain rod with

    snap hooks, heavy plastic curtain, removable chrome plated strainer, [Fiat Pilot 99M32].

    .2 Trim: Concealed shower supply with lever handles, bent shower arm with adjustable

    spray ball joint shower head and escutcheon, [Chicago Faucet # 767-8-370CPR].

    .3 Trim: Concealed shower supply with thermostatic and pressure balancing mixing valves,

    bent shower arm with adjustable spray ball joint shower head and escutcheon, [Chicago

    Faucet # 2502-600CP].

    2.10 INSTITUTIONAL SHOWERS

    .1 Shower Head: Chrome Plated vandal-proof institutional head with integral wall bracket

    and built-in 0.19 L/s flow control, [Powers 141-381].

    .2 Trim: Concealed straight way pattern valve with indexed cross handle.

    .3 Control: Thermostatic cabinet supply fixture consisting of thermostatic mixing valve

    with union inlet strainer checkstops, volume and shut-off valve, horizontal stem diam

    thermometer, in recessed steel cabinet with baked enamel finish, [Powers Series 430

    Hydroguard].

    2.11 DRINKING FOUNTAIN

    .1 Fountain: Wall mounted, stainless steel with brushed satin finish, one piece backsplash

    and basin, hooded elevated antisquirt bubbler with stream guard, automatic stream

    regulator, push button actuation, mounting bracket, screwdriver stop, [Halsey Taylor #

    5701].

    .2 Fountain: Stainless steel with brushed satin finish, [semi-recessed] [fully-recessed] with

    elevated anti-squirt bubbler with stream guard, automatic stream regulator, push button

    actuation, access cover plate, mounting bracket, screwdriver stop, [Halsey Taylor # 5801]

    [Halsey Taylor # 8880].

    .3 Fountain: Surface mounted electric water cooler with stainless steel top, elevated

    anti-squirt bubbler with stream guard automatic stream regulator, mounting bracket, ARI

    capacity of [ ] L/s, [ ] kW.

     Section 15410

    Plan No: Plumbing Fixtures and Trim

    Project ID: Page 5

2.12 WASH FOUNTAINS

    .1 Bowl: Semi-circular, 900 mm diameter, [precast stone] [enamelled steel] [stainless steel],

    [Bradley Type WF].

    .2 Accessories: Foot controlled self-closing valve, spray head, liquid soap dispenser,

    manual mixing valve, supporting tube, spud and strainer, operating mechanism, foot

    levers and rail, combination stop, strainer and check valves.

2.13 SERVICE OR MOP SINKS

    .1 Bowl: 550 x 450 x 300 mm deep, stain resisting, porcelain enamelled inside only, cast

    iron roll-rim sink with 300 mm high back concealed hanger, chrome plated strainer, cast

    iron P-trap with adjustable floor flange, [Crane 7-566].

    .2 Bowl: 900 x 600 x 250 mm deep white moulded stone, floor mounted sink with 25 mm

    wide shoulders, SS strainer, [Fiat MSB-3624.]

    .3 Trim: Exposed wall type supply with cross handles, spout wall brace, vacuum breaker,

    hose, end spout, strainers, eccentric adjustable inlets, integral screwdriver stops with

    covering caps and adjustable threaded wall flanges, [Chicago Faucet # 897CP] 1.5 m of

    15 mm plain end reinforced rubber hose, hose clamp, mop hanger.

2.14 THERMOSTATIC MIXING VALVE

    .1 Provide thermostatic mixing valve capacity [ ] L/s at [ ] kPa differential. Provide

    thermostatic valve complete with check valve, volume control shut-off valve on outlet,

    stem type thermometer on outlet, strainer stop check on inlet, mounted in lockable

    cabinet of 1.6 mm prime coated steel.

3. Execution

3.1 INSTALLATION

    .1 Install each fixture with its own trap, easily removable for servicing and cleaning. At

    completion thoroughly clean plumbing fixtures and equipment.

    .2 Provide chrome plated rigid or flexible supplies to fixtures with screwdriver stops,

    reducers and escutcheons.

    .3 Install wall mounted lavatories, urinals and water closets with approved wall carriers,

    model to suit installation.

     Section 15410

    Plan No: Plumbing Fixtures and Trim

    Project ID: Page 6

    .4 Mount fixtures the following heights above finished floor:

     Water Closet:

     Standard 380 mm to top of bowl rim.

     Handicapped 450 mm to top of seat.

     Urinal:

     Standard 550 mm to top of bowl rim.

     Handicapped 480 mm to top of bowl rim.

     Lavatory:

     Standard 780 mm to top of basin rim.

     Handicapped 800 mm to top of basin rim.

     Drinking Fountain:

     Standard [750 mm] [1000 mm] to top of basin rim.

     Handicapped 900 mm to top of basin rim.

     Water Closet Flush Valves:

     Standard 280 mm minimum above bowl rim.

     Recessed 250 mm minimum above bowl rim.

    .5 Solidly attach floor mounted water closets to floor with lag screws. Lead flashing shall

    not hold closet in place.

    .6 Install hose and faucets and hose connections with vacuum breakers.

    .7 Provide on lab sinks polyethylene or PVC-DWV drain and vent lines with glass 450 mL

    bottle trap. Run plastic drain to floor and approved piping under slab. Run plastic vents

    to main header on roof terminal.

3.2 PROTECTION

    .1 Protect fixtures against use and damage during construction.

     Section 15410 Plan No: Plumbing Fixtures and Trim Project ID: Page 7

3.3 FIXTURES ROUGH-IN SCHEDULE

    .1 Rough-in fixture piping connections in accordance with following table of minimum

    sizes or as required for particular fixtures.

    Hot Water Cold Water Waste Vent

    Lavatories 15 mm 15 mm 40 mm 30 mm

    Service Sink 15 mm 15 mm 50 mm 40 mm

    Kitchen Sink 15 mm 15 mm 40 mm 30 mm

    Drinking Fountain - 15 mm 30 mm 30 mm

    Water Closet - 25 mm 100 mm 50 mm

    (Flush Valve)

    Water Closet - 15 mm 100 mm 50 mm

    (Tank Type)

    Urinals - 20 mm 50 mm 40 mm

    (Flush Valve)

    Urinal (Tank Type) - 15 mm 50 mm 40 mm

    Floor Drains - - 100 mm 40 mm

    Hose Bibbs 20 mm 20 mm

    END OF SECTION

Report this document

For any questions or suggestions please email
cust-service@docsford.com