DOCX

Control Cables - afranojancom

By Kristen Carroll,2014-08-09 11:47
9 views 0
Control Cables - afranojancom

    Conductors

    Conductors shall be Round Stranded, Class 2 as to IEC 60228. Solid Conductors Class 1 to IEC 60228

    can also be provided based on special request.

    Insulation

    XLPE Insulataion material and thickness shall be as per IEC 60502-1 rated 90;C for continuos operation.

    PVC Insulation material and thickness shall be as per IEC 60502-1 and BS 6346.PVC material shall be

    Type A as per IEC 60502-1 or TI1 as per BS 6346.

     PVC Insulation material as per SASO 1694 rated for 85?C continuous operation is also available upon

    Control Cables special request.

     Types of Control Cables

    Assembly 01.. Particulars & Guarantees Relating to PVC Insulating

    Compound (TYPE A) & (TYPE TI1)

     The Insulated cores are laid-up together with non-hygroscopic 02.. Particulars & Guarantees Relating to PVC Insulating fillers wherever necessary. The assembly is bedded with an Compound (SASO 1694) / Particulars & Guarantees

    Extruded layer of PVC. In case of non-armoured cables, this layer Relating to XLPE Insulation

     may be omitted provided the outer shape of the cables remains 03.. Particulars & Guarantees Relating to PVC Outer Sheath practically circular. TYPE ST2 (IEC 60502), TYPE 9 (BS 6755)

     04.. Copper Conductors, PVC Insulated, PVC Sheathed 1.5

    Colour Code mm?

     Colour code (1) is followed by all utilities in the Middle East and 05.. Copper Conductors, PVC Insulated, PVC Sheathed 2.5

    mm? colour of insulation for cables shall be as per mentioned below.

     However, cables as per colour code (2) mentioned below is also 06.. Copper Conductors, PVC Insulated, PVC Sheathed 4 mm? provided based on customer request.

     07.. Copper Conductors, XLPE Insulated, PVC Sheathed 1.5

    mm?

     08.. Copper Conductors, XLPE Insulated, PVC Sheathed 2.5

    mm?

     09.. Copper Conductors, XLPE Insulated, PVC Sheathed 4

     mm?

Colour Code (1) : Colour Code (2) :

    1 Core : Red or Black 1 Core : Brown or Blue

    2 Cores : Red, Black 2 Cores : Brown, Blue

    3 Cores : Red, Yellow, Blue 3 Cores : Brown, Black, Grey

    4 Cores : Red, Yellow, Blue, Black 4 Cores : Blue, Brown, Black, Grey

    5 Cores : Red, Yellow, Blue, Black, Green 5 Cores : Green/Yellow, Blue, Brown, Black, Grey Above 5 : Black Cores with White Numerals Above 5 : Black Cores with White numerals Cores Cores

Armor (Optional)

Armour shall comprise of either:

    Galvanized Steel Wires in accordance with IEC 60502-1 or BS 6346, or BS 5467 laid helically over PVC bedding as per requirement.

Galvanized Steel Tapes applied helically over the bedding in accordance with IEC 60502-1.

    Screening (Optional)

    ; Copper Tape(s) of nominal thickness 0.075 mm applied helically with suitable overlap. ; Copper Wires with copper tape binder (open helix) upon request.

    Outer Sheath

    Outer sheath shall be of Extruded PVC type ST2 as per IEC 60502-1 or Type 9 as BS 6346/5467. Special type of PVc sheathing material such as Fire Retardant PVC, Anti-termite PVC, Anti-Rodent PVC, Sunlight Resistant PVC, Oil Resistant PVC are available on special request. Also, special sheathing materials such as LLDPE, MDPE, HDPE, LSF, CPE are available on request.

Report this document

For any questions or suggestions please email