    Australian Government

     Department of Climate Change

     and Energy Efficiency

    Australian Government

    Home Insulation Program

    FOIL INSULATION

    ELECTRICAL SAFETY INSPECTION REPORT

    Record of Inspection and Testing

    Version 3

    Issued: 5 March 2010

    Australian Government

     Department of Climate Change

     and Energy Efficiency

Note for the householder:

    On 10 February 2010, the Australian Government announced that every home with

    foil insulation installed under the Australian Government‟s Home Insulation Program

    was eligible for an electrical safety inspection.

To have an inspection done, you must contact a licensed electrical contractor. They

    will inspect the foil installation and determine whether it is causing an electrical fault.

You should not enter your roof space for any reason until a licensed electrical

    contractor has inspected your home and rectified any electrical faults.

If the electrician identifies an electrical fault that has occurred as a result of the

    installation of foil insulation products under the Home Insulation Program, they will

    repair that fault. If they are unable to complete the repair work, it is their responsibility to ensure your house is left in a safe state and arrange a time to return and complete

    the work.

The electrician will then give you a copy of their assessment and report on the faults

    identified and all repair works undertaken. They will invoice the department for the

    reasonable costs of the inspection and the repair work.

Where pre-existing electrical faults or safety risks are identified that are NOT related

    to the installation of foil insulation under the Home Insulation Program, it is a matter

    for you and the electrician to discuss. You will need to pay for any repair work

    undertaken to address those faults. The department will still pay the reasonable

    costs of the inspection.

For more information visit the electrical safety page at

    www.environment.gov.au/energyefficiency or call 131 792.

Note: The Australian Government is not responsible for the licensed electrical contractor you

    select or their work and does not accept liability for any loss, damage, injury or cost incurred

    as a result of any act or omission of such a licensed electrical contractor.

     2

    Australian Government

     Department of Climate Change

     and Energy Efficiency

Note for the electrician:

    Electrical safety inspections are only available to householders who have had foil

    insulation installed under the Australian Government‟s Home Insulation Program.

You must obtain the householder‟s Program Reference Number (PRN).

    Householders would have received their PRN by phoning the 131 792 hotline, or

    through having received a letter from the department. You will not be paid for the

    inspection if you do not include the PRN on the attached form.

You must complete ALL aspects of this form, including details of how long it takes

    you to complete the inspection, any repair work undertaken, your usual hourly rate

    and the number of workers you have on the site. The department will pay the

    reasonable cost of the inspection, which is expected to be up to the value of $400

    (GST inclusive).

Reasonable costs of any electrical repair work required to address identified electrical

    faults caused by the installation of foil insulation under the Home Insulation Program

    will be paid for by the department at your usual hourly rate. You must clearly

    document the nature of the faults (including photographs) and the repairs on this

    form and the time taken to complete them.

Both you and the householder must fill out and sign the relevant declarations

    contained in the form.

The invoice itself must be addressed to:

    Department of the Environment, Water, Heritage and the Arts

    PO Box 787 Canberra ACT 2601; and

    ? state “Tax Invoice”

    ? include your ABN

    ? show the GST amount separately or state „GST inclusive‟

When completed, send this form and a correctly rendered invoice to the department

    at electricalinspections@environment.gov.au or

    Electrical Safety Inspections

    Energy Efficiency Task Force

    Department of the Environment, Water, Heritage and the Arts

    GPO Box 787

    CANBERRA ACT 2601

For more information visit the electrical safety page at

    www.environment.gov.au/energyefficiency or call 131 792.

Note: No employment or agency relationship exists between you and the Australian

    Government relating to your undertaking any electrical safety inspections or related work. The

    Australian Government is not responsible for you or your work and accepts no liability for any

    loss, damage, injury or cost incurred as a result of any act or omission by you. You should

    ensure you have appropriate insurance cover in relation to the risks associated with

    undertaking electrical safety inspections and related work.

     3

    Australian Government

     Department of Climate Change

     and Energy Efficiency

    Electrical Safety Inspection

    Foil Insulation

    Record of Inspection and Testing

    Version 3 Issued 5 March 2010

Program Reference Number:

    Note: This number can be obtained by calling 131 792 and providing name and address details for the household

    that has had foil insulation installed, or from a letter to the householder from the Department. Payment will not be made without this number.

Householder name

    Dwelling address

    Householder contact Tel: Mob: Date foil installed

    Dwelling age

Electrical contractor

    License number State Electrical worker 1 ………………………………………………………............ Name, license number,

    registered state/territory ………………………………………………………………..

    Electrical worker 2 ………………………………………………………............ Name, license number,

    registered state/territory ………………………………………………………………..

    Electrical worker 3 ………………………………………………………............ Name, license number,

    registered state/territory ………………………………………………………………..

    Date of inspection ………./………./……….

    Time Commenced: Completed: Hourly rate $ / hour

    Total costs Inspection $ Note: the Department will pay

    reasonable costs for the

    inspection which are expected Repair work $ to be up to $400 (GST

    inclusive).* Electrical repair

    work related to the foil

    insulation installation will be TOTAL $ paid at your usual hourly rate.

    * In exceptional circumstances higher claims may be considered.

     4

    Australian Government

     Department of Climate Change

     and Energy Efficiency

    Details of Inspection

IMPORTANT SAFETY NOTICE: TEST BEFORE YOU TOUCH!

    Electrical tests outlined in this procedure are intended to ascertain that the foil insulation is not in contact

    with live parts of the electrical installation. Electrical testing inherently involves a degree of hazard and this

    procedure involves a number of steps to be undertaken in the listed sequence in order to minimise the risk

    of electric shock to any person (electrician or householder) present on the premises. Variations to the

    procedure are permitted provided that an assessment, taking into account specific site conditions,

    confirms an equivalent safety outcome. Reference should be made to AS/NZS3017 Electrical installations

    Verification Guidelines, for further guidance on inspection and test practices.

    To alert of any electrical problems that may have arisen following STEP 1: Preparation/Assessment. the foil installation.

     Check when Comments/Concerns complete CONSULT the householder to confirm:

    ? approximate age of house; ? that foil insulation has been installed in

    the roof;

    ? if foil installer mentioned any electrical

    problems ? if any electrical faults (eg lights flickering,

    tingles from taps) have been observed

    since the roof was insulated

    ? acceptance that supply will be

    disconnected during Inspection/Test

    Conduct a VISUAL CHECK:

    Comment: ____________________ ? all isolators, circuit-breakers and fuses

     are ON

    Comment: ____________________ ? if RCDs (Residual Current Devices) are

     installed at switchboard

    Comment: ____________________ ? general condition of switchboard equipment Comment: ____________________ ? location of aerial service connection to house (if applicable) Count: ____________________ ? Check/count downlights, exhaust fans

    and/or heat lamp/fan combinations

    Ensures that the circuits within the roof space are not Walk through the house and turn lights, fans interrupted by single or multi-way switches and other equipment in the roof space ON.

    To ensure that hazards specific to the installation are controlled. STEP 2: Risk Management

    Conduct a RISK ASSESSMENT including Check when Comments/Concerns complete the following factors:

    Complete contractor’s safe work documents or ? electric shock hazard from potentially attached assessment form to confirm risk control live foil measure(s) and to ensure that the work is performed ? type/condition of wiring to a safe system.

    It is expected that 2 electrical workers would be ? excessive heat in roof space involved in the conduct of this test for live parts.

     ? poor visibility in darkened space ALERT: If risk considered unacceptable to proceed ? fall through ceiling complete the Safety Incident Report identifying your

    concern(s).

     5

    Australian Government

     Department of Climate Change

     and Energy Efficiency

    Additional PPE will be necessary where the Prepare and use Personal Protective Equipment roof space temperature is high eg cooling vests (PPE) that would assist in avoiding contact with a or collars „live‟ surface, including:

    ? insulated gloves, safety glasses and hard hat ? insulated mat and covers;

    ? cotton long sleeve shirt and long pants

    ? fibreglass ladder

    This procedure is based on check that foil insulation may be STEP 3: Test Procedure „live‟ and is based on 2 people. Before entering roof space conduct Check when Comments/Concerns VOLTAGE TEST: complete

    Independent earth and voltmeter is preferred ? install temporary independent earth, eg as it does not depend on the foil being electrode driven into ground; separated from earthed equipment. ? connect a trailing lead from independent earth to terminal on voltage tester; For accurate measurements of ‘touch voltage’ ? check that voltage tester works correctly by refer to AS/NZS3017 connecting other lead to socket-outlet or switchboard equipment;

     ? without entering the roof space, and using Voltage measurements: insulating gloves, mat and covers to ____________________ reduce risk of contact, connect other test lead ____________________ from voltage tester to foil in the vicinity of the ____________________ roof access point.

    Voltage detected? ALERT: If voltage detected, you must use

     YES / NO alternative procedures outlined in Safety Incident Report to: Be aware that the cause may involve damage ? make safe; to the consumers mains and isolation will ? identify cause; involve disconnection at service connection ? repair or disconnect; point. ? record and notify incident and action taken.

    Disconnection at service connection point will If no voltage detected, isolate all circuits by allow the subsequent IR test to include ? turning the Main Switch OFF or removing consumers main active. service fuse(s) at external connection point (if permitted by energy distributor); and Isolation method used: _____________ ? turning OFF supplies from any alt. sources.

    Checks that the active or neutral conductors Conduct INSULATION RESISTANCE TEST : are not in contact with the foil insulation by ? disconnect MEN link at switchboard; methods such as: ? connect a trailing lead from one IR Tester - an alligator clip on the IR test lead terminal to the active conductor(s) at the load connected to a continuous foil layer near side terminals of the main switch or other the access point isolated point; - a probe such as an insulated conduit with ? before entering the roof space, repeat the conductive end piece to enable contact VOLTAGE TEST on the foil as a precautionary with separate sections of foil measure ? enter roof space to the extent necessary to perform test; IR measurements: ? connect a probe from the other IR Tester Active /Foil___________________ terminal to each sheet of the foil;

    ? measure insulation resistance between active conductors and each sheet of foil and record; IR measurements: ? change trailing lead connection from active Neutral/Foil__________________ conductors to neutral conductors at neutral link;

    NOTE: Low IR measurement between neutral ? measure insulation resistance between neutral and foil may indicate that foil is earthed. conductors and each sheet of foil and record. Disconnect the consumers main neutral and

    repeat IR test between circuit neutrals and foil

    and mains neutral and foil

     6

    Australian Government

     Department of Climate Change

     and Energy Efficiency

    Low IR may mean foil fixings have penetrated ALERT: If IR measurements are low cable and a safe procedure will need to be (acceptable values are >1.0MΩ), you must use conducted to identify and record cause. alternative procedures outlined in the Safety

     Incident Report to:

    (Check if ? make safe; applicable and ? identify cause; was completed) ? repair or disconnect;

    ? record and notify incident and action taken.

     If IR measurements are acceptable, restore

    supply to installation

    ? remove IR tester trailing lead;

     ? reconnect MEN link;

    (Check if ? turn main switch ON; applicable and ? check that supply restored to householder‟s was completed) equipment;

    ? repeat the VOLTAGE TEST on the foil before

    disconnecting independent earth

    Were covers installed around electrical YES / NO accessories as noted in clause 4.5.2.3 of If no, install suitable covers or cut/move (Check once all AS3000:2007 AMdt1? Visually check for foil insulation to ensure compliance with are compliant) compliance behind every recessed light. relevant clearance requirements. Were any defects identified during testing? YES / NO Insert brief description in comments box. (Check if defects were identified)

    Were any defects related to the installation of foil YES / NO insulation?

    (Check if defects If yes, attach photographs. were related to If no, advise householder of pre-existing insulation) defect(s).

    Were any repairs conducted for defects relating YES / NO to the installation of foil insulation? If yes, provide further details in the table (Check if repairs overleaf. were undertaken)

    Record results of inspection/test and observations. STEP 4: Completion Documentation

    Check when Observations on Foil Insulation Comments/Concerns complete

    Fixed by metal staples or fasteners. Metal fixings: YES / NO

    YES / NO Comment: ___________ Measures taken to avoid contact with electrical

    wiring and equipment.

    YES / NO Comment: ___________ Foil insulation is covering/non-compliant distance from halogen or incandescent downlights;

    If yes, install suitable covers or cut/move foil to and/or ensure compliance with relevant clearance Airflow of exhaust fans/combinations is requirements. obstructed.

     YES / NO Comment: ___________Other concerns.

    Include photographs to identify specific

    concerns.

     7

    Australian Government

     Department of Climate Change

     and Energy Efficiency

     Good General quality/standard of foil installation.

     Poor- not fixed, gaps present If the foil insulation installation appears immediately dangerous, document concerns Repair required on safety grounds (including photographs) and repair, remove or Removal required on safety grounds otherwise make safe.

     Observations of Electrical Installation Comment: _____________________________________? general condition _____________________________________ _____________________________________ ? any immediately dangerous aspects If installation appears dangerous to use encountered that should require installation to complete the Safety Incident Report identifying

    concern, and rectify, disconnect or otherwise be disconnected/rectified make safe.

    Safety switches are in place and functioning for YES / NO

    all final sub-circuits and sub-mains located in the Comment: _________________________ ceiling space. _________________________________ Is consumer mains present in roof space? YES / NO

     Comment: _________________________ If yes, ensure physical separation or other _________________________________ appropriate protection from foil insulation.

    Attach notification of inspection/test in switchboard.

    Provide an additional comments here.

CERTIFICATION

    I certify that an electrical inspection and testing procedure, restricted to an assessment of the potential

    adverse effects of reflective foil insulation on the electrical installation, has been carried out on these

    premises in accordance with the nominated procedures.

    Electrician performing test: __________________________ License number _______________

    Signature: _____________________________Date:___________________

If you find non-conforming electrical work report this immediately to the relevant state or territory

    authority. Only correct non-conforming work if allowed to do so by the authorities. You may need to

    disconnect and make safe some parts of the installation

     8

    Australian Government

     Department of Climate Change

     and Energy Efficiency

    SAFETY INCIDENT REPORT

    (including details of repairs conducted)

    Description of repair Cause: Time taken

    Please circle

     Insulation

     Other

     Insulation

     Other

     Insulation

     Other

     Insulation

     Other

     Insulation

     Other

     Insulation

     Other

     9

    Australian Government

     Department of Climate Change

     and Energy Efficiency

    Declarations

Householders use only

I am the owner of the dwelling (or the authorised representative of the owner and have authority to legally

    bind the owner including the giving of the release herein)

    Name: ______________________________________

    of (address of dwelling):________________________________________________________________

     State: __________________ Postcode:___ ___ ___ ___ I understand that (name of electrician performing test)

    _______________________________________________________________ has conducted an electrical

    inspection and testing procedure, restricted to an assessment of the potential adverse effects of reflective foil insulation on the electrical installation, at my dwelling today.

    I have read the note for the householder (page 2).

    I understand by signing this document, I am agreeing to authorise the Australian Government to pay for this

    service conducted today at my dwelling. I release the Australian Government from all liability for any loss,

    damage, injury or cost incurred as a result of, or relating to the electrical safety inspection and related work.

    Signature of owner/authorised representative Witness (electrician performing test)

    …………………………………… ……………………………………

….../……./…… ….../……./……

Licensed electrician’s use only